TNR-B30
Application scope

         TNR-B/C/D series surge protector is designed and manufactured according to GB18802.1-2011/IEC61643-1:2005. It is used in AC 47-63Hz's TT, IT and TN power supply system, which is used for T2 class II protection. It prevents all kinds of electronic and electrical equipment from being damaged by lightning overvoltage.

         TNR-B, C series protectors are mostly used to distribution box protection in electric box and low voltage switchgear cabinet.

         TNR-D series protection and electrical equipment terminal protection, can be installed in the electronic and electrical equipment, distribution box, communication equipment.

Installation matters

         A failure from overheating, indicating a surge protector caused by the deterioration of the breakdown, the failure from the device can automatically from the from the grid, and show the red (window) signal (normal window green), which indicates that the protector has failure need to be changed.

        Two. Remote signal warning device:

        Normal open and normal close . When one or more modules fail, the state of the terminal is turned over. The rated capacity of the terminal: 250V/3 (0.5) A.
 

Product features

1. The high efficient varistor is used, and the response time is fast.

2. It is suitable for the power supply system such as TT/IT/TN, which is used for T2 protection.

3, with remote signal alarm contact, remote monitoring protector installed state;

4, the impact flow rate is large and the residual pressure is low.

5, the standard 35mm rail installation;

6. The installation is convenient and the maintenance is simple.

technical data
Electrical parameters technical data
Maximum continuous operating voltage Uc(V~) 385/440
Nominal discharge current(8/20us) 30
Maximum discharge current(8/20us) 60
Protection level Up(kV) <2.2/2.5
response time(ns) <25
General parameters
Outer size(Width * height * depth) 72X90X65
Intercepting area of access wire(mm²) ≥10
Access ground intercepting area(mm²) ≥16
SPD special backup protector (disconnector) limp(kA) 80
work environment -40~+70℃,relative humidity<(25℃ below) 
telecommunication equipment 11.14 Normal open;11.12 Normal closed