PRODUCTS
HOME - PRODUCTS - PV system solar energy surge protective devices
Surge protection of photovoltaic power generation system
Model description
Configuration description of surge protection
Configuration description of surge protection Effect Choice Explain
A Protection of solar panels LT-60/G or LT-80/G The connection line with the solar panel should be as short and straight as possible. According to the specific environment, the surge protector should be installed in the waterproof box.
B Lightning protection of solar panel and controller LT-40/G The connection to the grounding line and the connection to the grounding wire of the DC side inverter should be as short as possible.
C Lightning protection of controller and inverter LT-40/G The connection to the grounding line and the connection to the grounding wire of the DC side inverter should be as short as possible.
D/E Protection of inverter AC output terminal

TNR-C20/385

TNR-B60/385

The connection to the earthing row should be as short as possible.
F Direct lightning protection TNR-FB There should be special earthing and grounding wire.


Installation position discharge current Voltage selection Protection mode Raiter model
A

ln

20kA

40kA

60kA

Selecting the battery voltage according to the actual battery Selecting the battery voltage according to the actual battery LT-40G
B LT-80G
C LT-100G


Model / parameter Rated working voltage Un(V-) Maximum continuous operating voltage Uc(V-) Nominal discharge current ln(kA) Maximum discharge current lmax(kA) Pattern structure Scope of application Wiring diagram
LT-40/G48L 48 65 20KA 40KA Type L Below 100V system  
LT-40/G100L 100 135
LT-80/G48L 48 65 40KA 80KA
LT-80/G100L 100 135
LT-100/G48L 48 65 60KA 100KA
LT-100/G100L 100 135
LT-40/G360U 360 500 20KA 40KA Type U 120V to 500V system  
LT-40/G470U 470 600
LT-80/G360U 360 500 40KA 80KA
LT-80/G470U 470 600
LT-100/G360U 360 500 60KA 100KA
LT-100/G470U 470 600
LT-40/G500YU 500 650 20KA 40KA Type Y(Band discharge tube) 500V to 700V system  
LT-40/G680YU 680 900
LT-80/G500YU 500 650 40KA 80KA
LT-80/G680YU 680 900
LT-100/G500YU 500 650 60KA 100KA
LT-100/G680YU 680 900
LT-40/G900Y 900 1200 20KA 40KA Y type (no discharge tube) Over 700V system  
LT-40/G1000Y 1000 1300
LT-80/G900Y 900 1200 40KA 80KA
LT-80/G1000Y 1000 1300
LT-100/G900Y 900 1200 60KA 100KA
LT-100/G1000Y 1000 1300

Note 1:G represents a surge protector for photovoltaic system

Note 2: at the end of the list of voltage levels, please explain the order

Note 3: signal control and detection surge protector please refer to the information of the signal product

Solar energy generating diagram
Shape and size diagram