Application scope

           LT series surge protective devices are designed and manufactured according to GB18802.1-2011 and IEC616343-1:2005. They are suitable for AC 47-63Hz's power supply system such as TT, IT and TN, so as to prevent all kinds of electronic and electrical equipment from being damaged by lightning overvoltage.
 

Working principle

          Under normal conditions, the surge protector is in a high resistance state. When the surge or overvoltage occurs due to lightning or other reasons, the protector will rapidly lead in the nanosecond time, and the surge and overvoltage will be introduced into the earth, thus protecting the power equipment on the grid. When the surge overvoltage is disappearing, the protector is restored to a high resistance state. It does not affect the normal operation of the power grid and equipment.
 

technical parameter

Model LT-200 LT-100 LT-80 LT-40 LT-20 LT-10
Maximum continuous operating voltage Uc(V~) 385/440 385/440 385/440 385/440 385/440 320/385
Nominal discharge current  In(kA) 100 60 40 20 10 5
Maximum discharge current lmax(kA) 160 100 80 40 20 10
Protection level Up(kA) <2.5/3.0 <2.5/3.0 <2.5/3.0 1.8/2.2 1.6/1.8 1.4/1.5
response time t(ns) <25 <25 <25 <25 <25 <25
Intercepting area of access wire (mm²) ≥16 ≥16 ≥10 ≥6 ≥6 ≥4
Intercepting area of grounding wire (mm²) ≥25 ≥25 ≥16 ≥10 ≥10 ≥6
Anterior recommendation series fuse (A) 320 250 125 63 40 32
work environment (℃) -40~+70℃
relative humidity ≤95%(25℃)
Product connection and size